Climate Control
USEFUL ELECTRICAL FORMULAS
To Obtain
Single Phase AC
Three Phase AC
Kilowatts
Volts x Amps x PF
1000
1.732 x Volts x Amps x PF
1000
kVA
Volts x Amps
1000
1.732 x Volts x Amps
1000
Amperes when motor hp known
HP x 746
Volts x PF x Efficiency
HP x 746
1.732 x Volts x PF x Efficiency
Amperes when kW known
kW x 1000
Volts x PF
kW x 1000
1.732 x Volts x PF
Amperes when kVA known
kVA x 1000
Volts
kVA x 1000
1.732 xVolts